                                Thermal Imaging - Electrical


                                Non Destructive Testing - Electrical 
                                Thermal Imaging is the leading non-destructive testing tool used in elrctrical switchboard maintenance and switchgear maintenance. It is an excellent fire prevention tool used to identify 'hot joints' invisible to the human eye. It is an essential part of every commercial and industrial business’s preventative maintenance plan.
                                Extreme Electrical Fault
                                This extreme fault was picked up during a routine scan. Fire danger was extreme causing an immediate shut-down of the plant.
                                Picture
                                What You See
                                Picture
                                What We See
                                Picture
                                Temperature Graphic read from the three lines on the Thermal Image on the immediate left
                                Extreme Electrical Fault
                                Fuse links and Power Factor Correction units are the most common electrical fault we find in manufacturing plants, hi-rise buildings and hotels.

                                The following is a fault found in a Power Factor Correction unit. 
                                Picture
                                What You See
                                Picture
                                What We See
                                Picture
                                Temperature Graphic read from the two lines on the Thermal Image on the immediate left

                                Minor Electrical Fault
                                Smaller faults develop without your knowledge Thermal Imaging will find fire danger.
                                Picture
                                What You See
                                Picture
                                What We See
                                Picture

                                Temperature Graphic read from the two lines on the Thermal Image on the immediate left
                                Eddy Current effects
                                The following steel plate was installed in a switchgear cubicle. Hysteresis / Eddy current losses resulted in local heating. It was recomended the steel plate be replaced by stainless steel.
                                Picture
                                What You See
                                Picture
                                What We See
                                Picture

                                Temperature Graphic read from the two lines on the Thermal Image on the immediate left


                                Fire Danger
                                Complacency and bad OH&S procedure are the number 1 cause of fire. It is imperative to scan your plant annually.
                                Picture
                                Picture
                                Picture
                                Thermograph depicting overhearing fuse link and base
                                Picture
                                Picture
                                   Burned Fuse Link and Base              Fire in Main Switch Room

                                Some useful links:
                                Sydney shopping centre evacuated after fire
                                                                                    ABC News 
                                Substation Fire                                                                                             BBC
                                Hundreds evacuated in fire at Sydney shopping centre                                     news.com.au
                                Broadway Shopping Center Fire 
                                Motorists warned as Sydney factory fire still burns                                           SMH.com.au


                                Transformers or Static Machines
                                You cannot see the overheating transformer coils, but Thermal Imaging picked up these under-rated / overloaded transformers. All of the embedded temperature sensors had failed leading to fire danger, and costly downtime. 

                                Thermal Imaging predicted early failure of this air cooled transformer, preventing lift failure in a high rise building.
                                Picture
                                What You See
                                Picture
                                What We See
                                Picture

                                Temperature graphic read from the three lines on the picture immediately left 

                                Non Destructive Testing:  Electro-Mechanical
                                Motors

                                Thermal Imaging can pick up overheating motor bearings and other mechanical equipment. 